Development of a system for detecting and locating damaged insulator strings with signals collected at substations

dc.contributor.authorCapelini, Renato Massonispa
dc.date.accessioned2019-07-03T04:50:37Zspa
dc.date.available2019-07-03T04:50:37Zspa
dc.date.issued2015-01-01spa
dc.description.abstractThis paper presents a novel technique for remotely identifying and locating of damaged insulator strings based on an analysis of noise signals recorded on the ground connection of current transformers installed on transmission line substations. Damaged insulators usually present electrical surface activity. Surface and corona discharges may result in the generation of high frequency signals that can travel through the transmission line conductors, which are recorded by a data acquisition system. Each signal generated by the surface or corona discharge has a unique signature. This signature changes according to the position of the source, i.e., the damaged string along the line, which enables the association between the signal signature and the location of the string along the line. A method proposed to achieve this association is discussed in this paper as well as the tools and tests carried out during its development. An innovative way for capacitive coupling, which reduce detection system implementation costs is presentedspa
dc.description.abstractEste artículo presenta una nueva técnica para la identificación y la localización remota de las cadenas de aisladores dañadas basadas en el análisis de las señales de ruido registradas en la conexión a tierra de los transformadores de corriente instalados en subestaciones de línea de transmisión. Aisladores dañados suelen presentar actividad eléctrica superficial que pueden resultar en la generación de señales de alta frecuencia que pueden viajar a través de los conductores de la línea de transmisión y ser registrados por un sistema de adquisición de datos. Cada señal generada por la descarga superficial o corona tiene una firma única. Esta firma cambia con la posición de la fuente (aislador dañado) a lo largo de la línea, lo que hace posible la asociación entre la firma de la señal y la localización de la cadena a lo largo de la línea. Un método propuesto para lograr esta asociación se analiza en este trabajo, así como las herramientas y pruebas llevadas a cabo durante el desarrollo. Se utiliza una forma innovadora de acoplamiento capacitivo, lo que reduce los costos de implementación del sistema de detección.spa
dc.format.mimetypeapplication/pdfspa
dc.identifier.eprintshttp://bdigital.unal.edu.co/68709/spa
dc.identifier.issnISSN: 2248-8723spa
dc.identifier.urihttps://repositorio.unal.edu.co/handle/unal/67680
dc.language.isospaspa
dc.publisherUniversidad Nacional de Colombia - Sede Bogotá - Facultad de Ingenieríaspa
dc.relationhttps://revistas.unal.edu.co/index.php/ingeinv/article/view/41832spa
dc.relation.ispartofUniversidad Nacional de Colombia Revistas electrónicas UN Ingeniería e Investigaciónspa
dc.relation.ispartofIngeniería e Investigaciónspa
dc.relation.referencesCapelini, Renato Massoni (2015) Development of a system for detecting and locating damaged insulator strings with signals collected at substations. Ingeniería e Investigación, 35 (1). pp. 43-48. ISSN 2248-8723spa
dc.rightsDerechos reservados - Universidad Nacional de Colombiaspa
dc.rights.accessrightsinfo:eu-repo/semantics/openAccessspa
dc.rights.licenseAtribución-NoComercial 4.0 Internacionalspa
dc.rights.urihttp://creativecommons.org/licenses/by-nc/4.0/spa
dc.subject.ddc62 Ingeniería y operaciones afines / Engineeringspa
dc.subject.proposalinsulator stringsspa
dc.subject.proposaltransmission linespa
dc.subject.proposalneural networkspa
dc.subject.proposalcurrent transformerspa
dc.subject.proposalcadenas de aisladoresspa
dc.subject.proposallínea de transmisiónspa
dc.subject.proposalredes neuronalesspa
dc.subject.proposaltransformador de corrientespa
dc.titleDevelopment of a system for detecting and locating damaged insulator strings with signals collected at substationsspa
dc.typeArtículo de revistaspa
dc.type.coarhttp://purl.org/coar/resource_type/c_6501spa
dc.type.coarversionhttp://purl.org/coar/version/c_970fb48d4fbd8a85spa
dc.type.contentTextspa
dc.type.driverinfo:eu-repo/semantics/articlespa
dc.type.redcolhttp://purl.org/redcol/resource_type/ARTspa
dc.type.versioninfo:eu-repo/semantics/publishedVersionspa
oaire.accessrightshttp://purl.org/coar/access_right/c_abf2spa

Archivos

Bloque original

Mostrando 1 - 1 de 1
Cargando...
Miniatura
Nombre:
41832-244824-1-PB.pdf
Tamaño:
443.61 KB
Formato:
Adobe Portable Document Format